DUPLEX STACK MOUNTED COMPRESSED AIR PLANTS
WITH DESICCANT DRYERS
Furnish and install, where shown on the drawings a duplex stack mounted prefabricated medical compressed air plant with desiccant air dryers model____________ as manufactured by AMICO Corporation, Fairfield, NJ (1-800-935-3673)
The unit furnished shall be
a standard catalog item of the supplier regularly engaged in the business of
providing packaged systems for hospitals and laboratories and shall meet and
exceed the requirements of NFPA 99.
The package shall include
two oil-less air compressors and associated equipment, one vertical ASME tank
and one duplex control panel. The entire system including the receiver shall be
mounted on a common structural steel stack base. The system footprint shall not
exceed 82" x 60". The only field connections
required will be system intake, exhaust and power connection at the control
panel. All components shall be completely pre-piped and pre-wired to
single-point service connections. All interconnecting piping and wiring shall be
completed and operationally tested prior to shipment. Provide liquid tight
conduit, fittings and junction boxes for all control and power wiring.
The medical air compressors
shall be of the totally oil-less reciprocating air-cooled design. Connecting rod
and bearings shall be packed with lifetime lubrication and sealed.
Each compressor shall be
belt driven by a ____ HP, 3 phase, 60 cycle, ______ volt, 1750 RPM, ODP NEMA
construction motor. Slide bases for
convenient belt tension adjustment and totally enclosed OSHA approved belt
guards shall be provided.
Each air compressor shall
have a capacity of ________ SCFM at 100 PSIG.
The system shall include
individual compressor inline intake filters, discharge check valves of bronze
construction, safety relief valves, bronze intake and discharge flexible
connectors, solenoid unloaders, isolation valves, air cooled aftercoolers for
each compressor, high discharge temperature shut down switches on each cylinder,
pressure control switches, as well as copper tubing with shut-off cock for gauge
and switches. The system shall include a 120 gallon pressure storage tank of
ASME construction rated for 200 PSI MWP service. The tank shall be equipped with a pressure gauge, safety relief valve, 3
way by-pass, gauge glass and automatic electronic tank drain with manual
override. The inside of the tank shall be coated for rust protection with a two
component coating which provides a hard, durable lining. Provide spring
vibration isolators for each compressor.
The system shall include a
UL listed control panel in a NEMA 12 enclosure with the following accessories
for each pump:
Externally operable circuit
breaker with door interlock, control circuit transformer with fused primary
and secondary coils, H-O-A switch, magnetic starter with 3 leg overload
protection, hour meter and motor running light. Provide the panel with a
multiple position selector switch for selection of normal operation (automatic
alternation) or manual selection of lead and lag pumps if one of the pumps is
taken out of service due to scheduled maintenance. Provide audible and visual
local alarm (complete with indicating lights and individual sets of auxiliary
contacts wired to the terminal strip for remote alarm indication) for the
following: compressor temperature malfunction and reserve compressor in use.
Provide manual reset for thermal malfunction shut-down. All control and alarm
functions shall remain energized while any compressor in the system remains
electrically on-line. The lag compressor shall be able to start automatically if
the lead compressor fails to operate.
A completely packaged NFPA
99 and NEC compliant assembly featuring dual desiccant air dryers, dual 0.5
micron pre-filters, dual 0.5 micron after-filters, line pressure regulating
valves, dew point monitor, CO monitor and other accessories required to meet and
exceed the current code requirements shall be mounted on the compressor system
base. All components shall be completely pre-piped and pre-wired to single-point
service connections.
There shall be two identical banks of air treatment equipment, piped in parallel and provided with valves to by-pass either filter set for element replacement, maintenance and repair work on one of the sets while still treating medical compressed air through the other set without any sacrifice in air quality. Each bank consists of three stages of treatment.
The first stage is a
prime efficiency coalescer with particle removal down to 0.5 micron with
99.9999% retention. This filter removes aerosols and solid particles. The filter
is equipped with electronic drain and element change indicator.
The second stage is a
desiccant heatless air dryer, equipped with purge control. Pressure dew point of
+20oF is attained by
directing the flow of saturated compressed air over a bed of desiccant which is
contained in two separate but identical "twin" towers. Built-in purge
saver control will automatically minimize and adjust the amount of purge air to
match the variable air flow. The dry compressed air is discharged from the
"on line" tower into the third stage.
The third
stage is a prime efficiency particulate afterfilter with particle removal down
to 0.5 micron. The after filter element is provides high particle retention, low
pressure drop and long element life.
Downstream pressure
regulators will maintain constant discharge pressure of 55 PSIG (field adjustable).
Digital dew point and
CO monitors with alarm set points at +390F
and 10 PPM are provided with dry contacts for connection to remote alarm panels.
A "demand check" for maintenance is included per current NFPA 99 for
each instrument.
The compressed air system
shall be guaranteed in writing by the manufacturer for a period of 12 months
from the date of start-up or 18 months from the date of shipment (whichever
comes first) against defects in design, materials, or construction. In addition,
the compressors are guaranteed for 36 months from the date of shipment.
The service of a factory
trained representative shall be made available at the jobsite to check
installation, start-up and instruct operating personnel in the proper operation
and maintenance.